PARAENT

본문 바로가기 주메뉴 바로가기 서브메뉴 바로가기

E-Type

Economic Power Control
  • Digital Power Regulator having basic functions for general usage.
  • Control method changeable (Zero-Crossing ↔ Phase-Angle) to type of load.
카타로그 다운로드 메뉴얼 다운로드
Model SE (Single phase) TE (Three phase)
Rated voltage 110V / 220V / 380V / 440V 110V / 220V / 380V / 440V
Allowance of voltage ±10% of rated voltage ±10% of rated voltage
Rated current 25A / 40A / 55A / 70A 25A / 40A / 55A / 70A
Frequency 50/60Hz (Auto selectable) 50/60Hz (Auto selectable)
Minimum load 1A 1A
Output range Phase-Angle : 0~97%
Zero-Crossing : 0~100%
Phase-Angle : 0~97%
Zero-Crossing : 0~100%
PCB power source Same as main power Same as main power
Power consumption Less than 5W (Without cooling fan) Less than 8W (Without cooling fan)
Input signal Auto : 4~20mA (Default) / 0~10VDC / 1~5VDC :Option
Manual : 10KΩ potentiometer
Auto : 4~20mA (Default) / 0~10VDC / 1~5VDC :Option
Manual : 10KΩ potentiometer
Output relay N.O. 1CH (Changeable to N.C. when ordering) N.O. 1CH (Changeable to N.C. when ordering)
Control method Phase-Angle /
Zero-Crossing with compensation algorithm
Phase-Angle /
Zero-Crossing with compensation algorithm
Cooling Option 25A, 40A : Natural cooling (Option : cooing fan)
55A, 70A : Cooling fan installed
Alarm Over Current, Over Temperature of heatsink(60℃, 80℃),
Fuse failure, Load failure, SCR failure
Over Current, Over Temperature of heatsink(60℃, 80℃),
Fuse failure, Load Failure, SCR failure, Unbalanced Load
Ambient Temp 0 ~ 40℃ 0 ~ 40℃
Humidity 40% ~ 85% RH (No condensation) 40% ~ 85% RH (No condensation)
Display 1 Three color LED 1 Three color LED
Net Weight 1.5Kgs(Without fan) / 1.7Kgs (With fan) 3.6Kgs (Without fan) / 3.9Kgs (With fan)